Customer: Cybenetics LTD
Syrou 6, Latsia, 2231, Nicosia Cyprus

Sigma F12 BK ARGB

Report Number: 26FN252A
Customer ID: 206
Lab ID: CYFAN00252

Test Results Report

Section A: Noise Testing Equipment

Test Environment Hemi-Anechoic Chamber with 6 dB(A) noise floor
Conditions 25(±2) degrees Celsius, 40-50% humidity
Sound Analyzer Bruel & Kjaer 2270-S G4 & 2250-L G4
Microphone Bruel & Kjaer Type 4955-A
Mic Calibrator Bruel & Kjaer Type 4231
Data Logger Picoscope TC-08
Testing Methodology Cybenetics Phi Fan Performance Standard

Section B: Fan Testing Equipment Technical Specifications

Manufacturer Long Win Science & Technology Corporation
Model Number LW-9266
Air Flow Rate 2.4 – 250 CFM
Accuracy of Air Flow Rate < 3.5% INFS
Repeatability error < 2%
Static pressure 0-20mmAq (100mmAq with the high static pressure throttle device)
Overall Dimensions 0.7 (W) x 2.2 (L) x 1.6 (H) m
Power Source 220VAC, 5A, Single Phase, 50/60Hz
Based on Standards ISO 5801-2007, AMCA 210-0, ASHRAE 51-2007, IEC 61591-2005, GB/T 1236-200

Section C: PHI Performance Levels

25dBAP Max1.03
25dBAQ Max35.00

Section D: Information about DUT

Product Identification Details
BrandOcypus
ModelSigma F12 BK ARGB
Serial NumberSF12BAHC0700964
Product Specifications
Manufacturer
BearingFluid Dynamic
ConnectorPWM
Cable length (mm)610
Daisy-chainCable
RGB Connector5V ARGB
RGB Daisy-chainCable
Cybenetics
Max Speed (RPM)2094
Max Airflow (CFM)60.50
Max Static Pressure (mmAq)2.89
Max Fan Noise Level (dBA)38.80
Fan Max Current (A)0.23
Fan Weight (gr)172
Dimensions (W x H x D)120mm x 120mm x 25mm
Cybenetics Testing Information
Lab IDCYFAN00252
Date of receiptAug 18, 2026
Testing DateNov 11, 2026
Report Issued DateNov 11, 2026
Engineer NameEfstathios Papadopoulos

Section E: Uncertainty

Fan Performance Uncertainty Estimation

General Statement

Measurement uncertainty associated with the reported results was evaluated and estimated in accordance with JCGM 100:2008 (Guide to the Expression of Uncertainty in Measurement — GUM) and ISO/IEC 17025:2017, Clauses 7.6 and 7.2.

The uncertainty budget accounts for all significant identified contributors arising from the measurement process, instrumentation, test conditions, and operator interaction.

The reported expanded uncertainty U is obtained by multiplying the combined standard uncertainty uc by a coverage factor k = 2, corresponding to a confidence level of approximately 95 %, assuming a normal probability distribution.

Unless otherwise stated, the reported uncertainty applies only to the specific measurements performed and does not include long-term drift, aging effects, or future environmental changes.

Expanded Measurement Uncertainty by Measurement Type

Measurement Expanded Uncertainty U (k=2, norm)
Fan Air Flow ±1.23176 % of reading (k=2) — e.g. ±3.69 CFM at 25 CFM, ±4.29 at 92 CFM, ±7.15 at 250 CFM
Fan Static Pressure ±0.6727 Pa

Air flow uncertainty is relative to the reading: U(Q) = 2·√[(1.8200)² + (0.0123176·Q)²] CFM, valid over the declared measuring range 2.4 – 250 CFM.

The reported static pressure uncertainty applies over the 0 – 20 mmAq (0 – 196.1 Pa) measuring range of the Long Win LW-9266 apparatus. The apparatus can be extended to 100 mmAq (981 Pa) with the high static pressure throttle device; the uncertainty of that extended range has not been separately verified and the value stated above does not apply to it.